3) Separation of the strands of cable cores may be prevented by?
单选
(I) Soldering or fitting core lugs;
(II) Twisting the strands;
(III) Fitting cable lugs or core-end sleeves;✓ 正确答案
(IV) Soldering the strands.
4) A cable gland marked with a suffix ‘X’ may only be used with?
单选
(I) Portable equipment with additional clamping of the cable;
(II) Fixed equipment with additional clamping of the cable;✓ 正确答案
(III) An enclosure also marked with a suffix ‘X’;
(IV) Fixed equipment.
1) The minimum cross-sectional area for aluminium conductors of cables (except IS cables) used in hazardous areas should hot be less than?
单选
(I) 25mm;
(II) 16mm;✓ 正确答案
(III) 10mm;
(IV) 6mm
12) Before work is carried out in an hazardous location which one of the following is necessary to understand?
单选
(I) The manufacturer’s documentation;
(II) The basic requirements for working in the zones of hazardous areas✓ 正确答案
(III) Circuit diagrams for panel wiring;
(IV) How the equipment operates;
10) Which one of the following statements represents the assessment requirements for technicians as given in BS EN60079-14 :
单选
(I) A degree in electrical engineering;
(II)Evidence only of having the necessary skills for the scope of work;
(III) Evidence only of having the necessary skills for the scope of work and competence across the range activities
(IV) Evidence indicating the necessary skills for the scope of work, competence across the range of activities and relevant knowledge and understanding✓ 正确答案